Recommended Wiring
Rules of Wiring and Shielding
Noise is always present in a system that involves both high power and small
signal circuitry. Regardless of the power configuration used for your system,
there are some wiring and shielding rules that should be followed to keep the
noise-to-signal ratio as small as possible.
Rules of Wiring
Power supply and motor wiring should be shielded twisted
pairs run separately from signal carrying wires.
A minimum of 1 twist per inch is recommended.
Motor wiring should be shielded twisted pairs using 20-gauge
wire or, for distance greater than 5 feet, 18 gauge or better.
Power ground return should be as short as possible to
established ground.
Power supply wiring should be shielded twisted pairs. Use
18 gauge wire if load is less than 4 amps, or 16 gauge for
more than 4 amps.
Do not Daisy-Chain power wiring to system components.
Rules of Shielding
The shield must be tied to zero-signal reference potential. In
order for shielding to be effective, it is necessary for the
signal to be earthed or grounded.
Do not assume that earth ground is true earth ground.
Depending on the distance to the main power cabinet, it
may be necessary to sink a ground rod at a critical location.
The shield must be connected so that shield currents drain
to signal-earth connections.
The number of separate shields required in a system is equal
to the number of independent signals being processed plus
one for each power entrance.
The shield should be tied to a single point to prevent ground loops.
A second shield can be used over the primary shield,
however, the second shield is tied to ground at both ends.
Recommended Power Supply Cables
Power supply cables must not run parallel to logic level wiring as noise will be
coupled onto the logic signals from the power supply cables. If more than one
driver is to be connected to the same power supply, run separate power and